{"id":1751,"date":"2014-04-08T13:30:03","date_gmt":"2014-04-08T17:30:03","guid":{"rendered":"http:\/\/www.constructionspecifier.com\/?p=1751"},"modified":"2017-01-17T14:23:33","modified_gmt":"2017-01-17T19:23:33","slug":"impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies","status":"publish","type":"post","link":"https:\/\/www.constructionspecifier.com\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\/","title":{"rendered":"Impactable Dock Doors: <i>Florida Building Code<\/i> (<i>FBC<\/i>) 1715.5.3, \u201cExterior Door Assemblies\u201d"},"content":{"rendered":"<p><strong>by Josh Brown<br \/>\n<\/strong>Exterior door assemblies not covered by <i>Florida Building Code<\/i> (<i>FBC<\/i>) 1715.5.2, \u201cExterior Windows, Siding, and Patio Glass,\u201d or <i>FBC<\/i> 1715.5.3.1, \u201cExterior Door Assemblies,\u201d shall be tested for structural integrity in accordance with Procedure A of ASTM E330, <i>Standard Test Method for Structural Performance of Exterior Windows, Doors, Skylight,s and Curtain Walls by Uniform Static Air Pressure Difference<\/i>, at a load of 1.5 times the required design pressure load. The load shall be sustained for 10 seconds with no permanent deformation of any main frame or panel member in excess of 0.4 percent of its span after the load is removed. The design pressures, as determined from American Society of Civil Engineers (ASCE) 7, <i>Minimum Design Loads for Buildings and Other Structures,<\/i> are permitted to be multiplied by 0.6. High-velocity hurricane zones (HVHZ) must comply with Testing Application Standard (TAS) 202. After each specified loading, there must be no glass breakage, permanent damage to fasteners, hardware parts, or any other damage that causes the door to be inoperable.<\/p>\n<p>The exceptions include:<\/p>\n<ol>\n<li>Door assemblies installed in nonhabitable areas where the door assembly and area are designed to accept water infiltration, need not be tested for water infiltration.<\/li>\n<li>Door assemblies installed where the overhang (OH) ratio is equal to or more than 1 need not be tested for water infiltration. The overhang ratio shall be calculated by the following equation:<\/li>\n<\/ol>\n<p><span style=\"font-size: medium; font-family: times new roman,times;\">OH ratio = OH Length\/OH Height where:<\/span><br \/>\n<span style=\"font-family: times new roman,times; font-size: medium;\"> OH Length = The horizontal measure of how far an overhang over a door projects out from the door\u2019s surface.<\/span><br \/>\n<span style=\"font-family: times new roman,times; font-size: medium;\"> OH Height = The vertical measure of the distance from the door\u2019s sill to the bottom of the overhang over a door.<\/span><\/p>\n<p>1715.5.3.1 Sectional garage doors and rolling doors shall be tested for determination of structural performance under uniform static air pressure difference in accordance with American National Standards Institute\/Door and Access Systems Manufactures Association (ANSI\/DASMA) 108, <i>Standard Method for Testing Sectional Garage Doors and Rolling Doors: Determination of Structural Performance Under Uniform Static Air Pressure Difference<\/i>, ASTM E330\u2019s Procedure A, or TAS 202. For products tested in accordance with ASTM E330, testing shall include a load of 1.5 times the required design pressure load sustained for 10 seconds, and acceptance criteria shall be in accordance with ANSI\/DASMA 108. (HVHZ shall comply with TAS 202.)<\/p>\n<p>Design pressures shall be determined from Table 1609.7(1) or ASCE 7. The design pressures, as determined from ASCE 7, are permitted to be multiplied by 0.6.<\/p>\n<p>The Miami-Dade County Building and Neighborhood Compliance (BNC) Department set out to ensure the strictest standards for manufacturers, including those for the overhead sectional doors used at many warehouse and distribution facilities. These standards require a notice of acceptance and completion of:<\/p>\n<ul>\n<li>air pressure test;<\/li>\n<li>large missile impact test;<\/li>\n<li>cyclic wind pressure loading test; and<\/li>\n<li>a forced entry test.<\/li>\n<\/ul>\n<p>To read the full article,&#8221;Impactable Dock Doors Help Increase Safety in Warehouses,&#8221; click <a href=\"http:\/\/www.constructionspecifier.com\/masterformat\/impactable-dock-doors-help-increase-safety-in-warehouses-2\/\">here<\/a>.<\/p>\n","protected":false},"excerpt":{"rendered":"<p>Exterior door assemblies not covered by <i>Florida Building Code<\/i> (<i>FBC<\/i>) 1715.5.2, \u201cExterior Windows, Siding, and Patio Glass,\u201d or <i>FBC<\/i> 1715.5.3.1, \u201cExterior Door Assemblies,\u201d shall be tested for structural integrity in accordance with Procedure A of ASTM E330, <i>Standard Test Method for Structural Performance of Exterior Windows, Doors, Skylight,s and Curtain Walls by Uniform Static Air Pressure Difference<\/i>, at a load of 1.5 times the required design pressure load.  <\/p>\n","protected":false},"author":4,"featured_media":0,"comment_status":"open","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[520,179,449,188,273,191,295,491,460],"tags":[559,565,560,561,562,563,564],"class_list":["post-1751","post","type-post","status-publish","format-standard","hentry","category-features","category-masterformat","category-uniformat","category-08-00-00-openings","category-08-10-00-doors-and-frames","category-11-00-00-equipment","category-11-10-00-vehicle-and-pedestrian-equipment","category-b2050exterior-doors-and-grilles","category-b20exterior-vertical-enclosures","tag-11-13-00-loading-dock-equipment","tag-b2050-40-exterior-special-function-doors","tag-high-wind-event","tag-impactable-dock-door","tag-loading-dock","tag-osha","tag-safety","entry"],"acf":[],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v28.8 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>Impactable Dock Doors: Florida Building Code (FBC) 1715.5.3, \u201cExterior Door Assemblies\u201d - The Construction Specifier<\/title>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/www.constructionspecifier.com\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\/\" \/>\n<meta property=\"og:locale\" content=\"en_US\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Impactable Dock Doors: Florida Building Code (FBC) 1715.5.3, \u201cExterior Door Assemblies\u201d - The Construction Specifier\" \/>\n<meta property=\"og:description\" content=\"Exterior door assemblies not covered by Florida Building Code (FBC) 1715.5.2, \u201cExterior Windows, Siding, and Patio Glass,\u201d or FBC 1715.5.3.1, \u201cExterior Door Assemblies,\u201d shall be tested for structural integrity in accordance with Procedure A of ASTM E330, Standard Test Method for Structural Performance of Exterior Windows, Doors, Skylight,s and Curtain Walls by Uniform Static Air Pressure Difference, at a load of 1.5 times the required design pressure load.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/www.constructionspecifier.com\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\/\" \/>\n<meta property=\"og:site_name\" content=\"The Construction Specifier\" \/>\n<meta property=\"article:published_time\" content=\"2014-04-08T17:30:03+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2017-01-17T19:23:33+00:00\" \/>\n<meta name=\"author\" content=\"Molly Doyle\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"Molly Doyle\" \/>\n\t<meta name=\"twitter:label2\" content=\"Est. reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"2 minutes\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\\\/\"},\"author\":{\"name\":\"Molly Doyle\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#\\\/schema\\\/person\\\/2fe1805293ddcc967e4bd9e8afc50294\"},\"headline\":\"Impactable Dock Doors: Florida Building Code (FBC) 1715.5.3, \u201cExterior Door Assemblies\u201d\",\"datePublished\":\"2014-04-08T17:30:03+00:00\",\"dateModified\":\"2017-01-17T19:23:33+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\\\/\"},\"wordCount\":477,\"commentCount\":0,\"publisher\":{\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#organization\"},\"keywords\":[\"11 13 00\u2014Loading Dock Equipment\",\"B2050.40\u2014Exterior Special Function Doors\",\"High-wind event\",\"Impactable dock door\",\"Loading dock\",\"OSHA\",\"Safety\"],\"articleSection\":[\"Features\",\"MasterFormat\",\"UniFormat\",\"08 00 00 Openings\",\"08 10 00 Doors and Frames\",\"11 00 00 Equipment\",\"11 10 00 Vehicle and Pedestrian Equipment\",\"B2050\u2212Exterior Doors and Grilles\",\"B20\u2212Exterior Vertical Enclosures\"],\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\\\/\\\/www.constructionspecifier.com\\\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\\\/#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\\\/\",\"url\":\"https:\\\/\\\/www.constructionspecifier.com\\\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\\\/\",\"name\":\"Impactable Dock Doors: Florida Building Code (FBC) 1715.5.3, \u201cExterior Door Assemblies\u201d - The Construction Specifier\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#website\"},\"datePublished\":\"2014-04-08T17:30:03+00:00\",\"dateModified\":\"2017-01-17T19:23:33+00:00\",\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\\\/#breadcrumb\"},\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/www.constructionspecifier.com\\\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\\\/\"]}]},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/www.constructionspecifier.com\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Impactable Dock Doors: Florida Building Code (FBC) 1715.5.3, \u201cExterior Door Assemblies\u201d\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#website\",\"url\":\"https:\\\/\\\/www.constructionspecifier.com\\\/\",\"name\":\"The Construction Specifier\",\"description\":\"Solutions for the Construction Industry\",\"publisher\":{\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#organization\"},\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/www.constructionspecifier.com\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-US\"},{\"@type\":\"Organization\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#organization\",\"name\":\"The Construction Specifier\",\"url\":\"https:\\\/\\\/www.constructionspecifier.com\\\/\",\"logo\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#\\\/schema\\\/logo\\\/image\\\/\",\"url\":\"https:\\\/\\\/www.constructionspecifier.com\\\/wp-content\\\/uploads\\\/2017\\\/09\\\/CS_Logo_BW_LR.jpg\",\"contentUrl\":\"https:\\\/\\\/www.constructionspecifier.com\\\/wp-content\\\/uploads\\\/2017\\\/09\\\/CS_Logo_BW_LR.jpg\",\"width\":288,\"height\":70,\"caption\":\"The Construction Specifier\"},\"image\":{\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#\\\/schema\\\/logo\\\/image\\\/\"}},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#\\\/schema\\\/person\\\/2fe1805293ddcc967e4bd9e8afc50294\",\"name\":\"Molly Doyle\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/b9db24e2e72277a0449a8b18be06d377923ec2d6246b36613db304f58b586baf?s=96&d=mm&r=g\",\"url\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/b9db24e2e72277a0449a8b18be06d377923ec2d6246b36613db304f58b586baf?s=96&d=mm&r=g\",\"contentUrl\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/b9db24e2e72277a0449a8b18be06d377923ec2d6246b36613db304f58b586baf?s=96&d=mm&r=g\",\"caption\":\"Molly Doyle\"},\"url\":\"https:\\\/\\\/www.constructionspecifier.com\\\/author\\\/molly\\\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Impactable Dock Doors: Florida Building Code (FBC) 1715.5.3, \u201cExterior Door Assemblies\u201d - The Construction Specifier","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.constructionspecifier.com\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\/","og_locale":"en_US","og_type":"article","og_title":"Impactable Dock Doors: Florida Building Code (FBC) 1715.5.3, \u201cExterior Door Assemblies\u201d - The Construction Specifier","og_description":"Exterior door assemblies not covered by Florida Building Code (FBC) 1715.5.2, \u201cExterior Windows, Siding, and Patio Glass,\u201d or FBC 1715.5.3.1, \u201cExterior Door Assemblies,\u201d shall be tested for structural integrity in accordance with Procedure A of ASTM E330, Standard Test Method for Structural Performance of Exterior Windows, Doors, Skylight,s and Curtain Walls by Uniform Static Air Pressure Difference, at a load of 1.5 times the required design pressure load.","og_url":"https:\/\/www.constructionspecifier.com\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\/","og_site_name":"The Construction Specifier","article_published_time":"2014-04-08T17:30:03+00:00","article_modified_time":"2017-01-17T19:23:33+00:00","author":"Molly Doyle","twitter_card":"summary_large_image","twitter_misc":{"Written by":"Molly Doyle","Est. reading time":"2 minutes"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.constructionspecifier.com\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\/#article","isPartOf":{"@id":"https:\/\/www.constructionspecifier.com\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\/"},"author":{"name":"Molly Doyle","@id":"https:\/\/www.constructionspecifier.com\/#\/schema\/person\/2fe1805293ddcc967e4bd9e8afc50294"},"headline":"Impactable Dock Doors: Florida Building Code (FBC) 1715.5.3, \u201cExterior Door Assemblies\u201d","datePublished":"2014-04-08T17:30:03+00:00","dateModified":"2017-01-17T19:23:33+00:00","mainEntityOfPage":{"@id":"https:\/\/www.constructionspecifier.com\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\/"},"wordCount":477,"commentCount":0,"publisher":{"@id":"https:\/\/www.constructionspecifier.com\/#organization"},"keywords":["11 13 00\u2014Loading Dock Equipment","B2050.40\u2014Exterior Special Function Doors","High-wind event","Impactable dock door","Loading dock","OSHA","Safety"],"articleSection":["Features","MasterFormat","UniFormat","08 00 00 Openings","08 10 00 Doors and Frames","11 00 00 Equipment","11 10 00 Vehicle and Pedestrian Equipment","B2050\u2212Exterior Doors and Grilles","B20\u2212Exterior Vertical Enclosures"],"inLanguage":"en-US","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/www.constructionspecifier.com\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\/#respond"]}]},{"@type":"WebPage","@id":"https:\/\/www.constructionspecifier.com\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\/","url":"https:\/\/www.constructionspecifier.com\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\/","name":"Impactable Dock Doors: Florida Building Code (FBC) 1715.5.3, \u201cExterior Door Assemblies\u201d - The Construction Specifier","isPartOf":{"@id":"https:\/\/www.constructionspecifier.com\/#website"},"datePublished":"2014-04-08T17:30:03+00:00","dateModified":"2017-01-17T19:23:33+00:00","breadcrumb":{"@id":"https:\/\/www.constructionspecifier.com\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\/#breadcrumb"},"inLanguage":"en-US","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.constructionspecifier.com\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\/"]}]},{"@type":"BreadcrumbList","@id":"https:\/\/www.constructionspecifier.com\/impactable-dock-doors-florida-building-code-fbc-1715-5-3-exterior-door-assemblies\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/www.constructionspecifier.com\/"},{"@type":"ListItem","position":2,"name":"Impactable Dock Doors: Florida Building Code (FBC) 1715.5.3, \u201cExterior Door Assemblies\u201d"}]},{"@type":"WebSite","@id":"https:\/\/www.constructionspecifier.com\/#website","url":"https:\/\/www.constructionspecifier.com\/","name":"The Construction Specifier","description":"Solutions for the Construction Industry","publisher":{"@id":"https:\/\/www.constructionspecifier.com\/#organization"},"potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.constructionspecifier.com\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-US"},{"@type":"Organization","@id":"https:\/\/www.constructionspecifier.com\/#organization","name":"The Construction Specifier","url":"https:\/\/www.constructionspecifier.com\/","logo":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/www.constructionspecifier.com\/#\/schema\/logo\/image\/","url":"https:\/\/www.constructionspecifier.com\/wp-content\/uploads\/2017\/09\/CS_Logo_BW_LR.jpg","contentUrl":"https:\/\/www.constructionspecifier.com\/wp-content\/uploads\/2017\/09\/CS_Logo_BW_LR.jpg","width":288,"height":70,"caption":"The Construction Specifier"},"image":{"@id":"https:\/\/www.constructionspecifier.com\/#\/schema\/logo\/image\/"}},{"@type":"Person","@id":"https:\/\/www.constructionspecifier.com\/#\/schema\/person\/2fe1805293ddcc967e4bd9e8afc50294","name":"Molly Doyle","image":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/secure.gravatar.com\/avatar\/b9db24e2e72277a0449a8b18be06d377923ec2d6246b36613db304f58b586baf?s=96&d=mm&r=g","url":"https:\/\/secure.gravatar.com\/avatar\/b9db24e2e72277a0449a8b18be06d377923ec2d6246b36613db304f58b586baf?s=96&d=mm&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/b9db24e2e72277a0449a8b18be06d377923ec2d6246b36613db304f58b586baf?s=96&d=mm&r=g","caption":"Molly Doyle"},"url":"https:\/\/www.constructionspecifier.com\/author\/molly\/"}]}},"views":8747,"publishpress_future_workflow_manual_trigger":{"enabledWorkflows":[]},"_links":{"self":[{"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/posts\/1751","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/users\/4"}],"replies":[{"embeddable":true,"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/comments?post=1751"}],"version-history":[{"count":5,"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/posts\/1751\/revisions"}],"predecessor-version":[{"id":25258,"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/posts\/1751\/revisions\/25258"}],"wp:attachment":[{"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/media?parent=1751"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/categories?post=1751"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/tags?post=1751"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}