{"id":3707,"date":"2013-07-12T16:13:58","date_gmt":"2013-07-12T20:13:58","guid":{"rendered":"http:\/\/www.constructionspecifier.com\/?p=3707"},"modified":"2014-05-12T16:22:50","modified_gmt":"2014-05-12T20:22:50","slug":"to-vent-or-not-to-vent-tips-for-insulating-vented-attics","status":"publish","type":"post","link":"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\/","title":{"rendered":"To Vent or Not to Vent: Tips for insulating vented attics"},"content":{"rendered":"<p>Areas to insulate include:<\/p>\n<ul>\n<li>exterior walls (<em>e.g.<\/em> dormer walls, portions of walls above ceilings of adjacent sections of split-level homes, unheated garages, and storage rooms);<\/li>\n<li>ceilings with cold spaces above, including dormer ceilings;<\/li>\n<li>knee walls of attic spaces finished as living quarters; and<\/li>\n<li>sloped walls and ceilings of attic spaces finished as living quarters.<\/li>\n<\/ul>\n<p>The U.S. Department of Energy\u2019s (DOE\u2019s) <em>Technology Fact Sheet on Ceilings and Attics<\/em> suggests when planning and managing vented ceiling insulation projects to ensure the following:<\/p>\n<ul>\n<li>ceiling is properly sealed;<\/li>\n<li>correct insulation levels are selected;<\/li>\n<li>insulation is properly installed; and<\/li>\n<li>attic ventilation is maintained.<\/li>\n<\/ul>\n<p>One should use more than a single layer of batt insulation on attic floors with conventional joists and rafters. The first layer is installed between the joists and should be the same height as the joists. The second layer is applied crosswise to the joists.<\/p>\n<p>In knee wall design, insulation should be kept from touching recessed light fixtures (unless they are rated for insulation contact).<\/p>\n<p>To read the full article, click <a href=\"http:\/\/www.constructionspecifier.com\/masterformat\/to-vent-or-not-to-vent-deciding-what-is-best-for-attic-applications\/\">here<\/a>.<\/p>\n<p>To read the other sidebar, click <a href=\"http:\/\/www.constructionspecifier.com\/masterformat\/to-vent-or-not-to-vent-qa\/\">here<\/a>.<\/p>\n","protected":false},"excerpt":{"rendered":"<p>Designers have long used cross-ventilation to minimize the potential for moisture accumulation and condensation in attics and crawl spaces. However, unvented attics have become popular in both residential and commercial applications, pushed by emerging claims of energy savings and moisture control. While these \u2018new-style\u2019 attics can be successfully used in many circumstances, this author believes there are reasons to employ vented assemblies in many situations.<\/p>\n","protected":false},"author":4,"featured_media":0,"comment_status":"open","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[179,449,187,268,487,459],"tags":[579,883,884,885,886,887,888],"class_list":["post-3707","post","type-post","status-publish","format-standard","hentry","category-masterformat","category-uniformat","category-07-00-00-thermal-and-moisture-protection","category-07-50-00-membrane-roofing","category-b1020roof-construction","category-b10superstructure","tag-07-57-13sprayed-polyurethane-foam-roofing","tag-b1020-90roof-construction-supplementary-components","tag-international-energy-conservation-code","tag-international-residential-code","tag-sprayed-polyurethane-foam","tag-unvented-attics","tag-vented-attics","entry"],"acf":[],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v28.9 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>To Vent or Not to Vent: Tips for insulating vented attics - The Construction Specifier<\/title>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\/\" \/>\n<meta property=\"og:locale\" content=\"en_US\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"To Vent or Not to Vent: Tips for insulating vented attics - The Construction Specifier\" \/>\n<meta property=\"og:description\" content=\"Designers have long used cross-ventilation to minimize the potential for moisture accumulation and condensation in attics and crawl spaces. However, unvented attics have become popular in both residential and commercial applications, pushed by emerging claims of energy savings and moisture control. While these \u2018new-style\u2019 attics can be successfully used in many circumstances, this author believes there are reasons to employ vented assemblies in many situations.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\/\" \/>\n<meta property=\"og:site_name\" content=\"The Construction Specifier\" \/>\n<meta property=\"article:published_time\" content=\"2013-07-12T20:13:58+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2014-05-12T20:22:50+00:00\" \/>\n<meta name=\"author\" content=\"Molly Doyle\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"Molly Doyle\" \/>\n\t<meta name=\"twitter:label2\" content=\"Est. reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"1 minute\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\\\/\"},\"author\":{\"name\":\"Molly Doyle\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#\\\/schema\\\/person\\\/2fe1805293ddcc967e4bd9e8afc50294\"},\"headline\":\"To Vent or Not to Vent: Tips for insulating vented attics\",\"datePublished\":\"2013-07-12T20:13:58+00:00\",\"dateModified\":\"2014-05-12T20:22:50+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\\\/\"},\"wordCount\":192,\"commentCount\":0,\"publisher\":{\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#organization\"},\"keywords\":[\"07 57 13?Sprayed Polyurethane Foam Roofing\",\"B1020.90?Roof Construction Supplementary Components\",\"International Energy Conservation Code\",\"International Residential Code\",\"Sprayed polyurethane foam\",\"Unvented attics\",\"Vented attics\"],\"articleSection\":[\"MasterFormat\",\"UniFormat\",\"07 00 00 Thermal and Moisture Protection\",\"07 50 00 Membrane Roofing\",\"B1020\u2212Roof Construction\",\"B10\u2212Superstructure\"],\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\\\/\\\/www.constructionspecifier.com\\\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\\\/#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\\\/\",\"url\":\"https:\\\/\\\/www.constructionspecifier.com\\\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\\\/\",\"name\":\"To Vent or Not to Vent: Tips for insulating vented attics - The Construction Specifier\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#website\"},\"datePublished\":\"2013-07-12T20:13:58+00:00\",\"dateModified\":\"2014-05-12T20:22:50+00:00\",\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\\\/#breadcrumb\"},\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/www.constructionspecifier.com\\\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\\\/\"]}]},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/www.constructionspecifier.com\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"To Vent or Not to Vent: Tips for insulating vented attics\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#website\",\"url\":\"https:\\\/\\\/www.constructionspecifier.com\\\/\",\"name\":\"The Construction Specifier\",\"description\":\"Solutions for the Construction Industry\",\"publisher\":{\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#organization\"},\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/www.constructionspecifier.com\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-US\"},{\"@type\":\"Organization\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#organization\",\"name\":\"The Construction Specifier\",\"url\":\"https:\\\/\\\/www.constructionspecifier.com\\\/\",\"logo\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#\\\/schema\\\/logo\\\/image\\\/\",\"url\":\"https:\\\/\\\/www.constructionspecifier.com\\\/wp-content\\\/uploads\\\/2017\\\/09\\\/CS_Logo_BW_LR.jpg\",\"contentUrl\":\"https:\\\/\\\/www.constructionspecifier.com\\\/wp-content\\\/uploads\\\/2017\\\/09\\\/CS_Logo_BW_LR.jpg\",\"width\":288,\"height\":70,\"caption\":\"The Construction Specifier\"},\"image\":{\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#\\\/schema\\\/logo\\\/image\\\/\"}},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#\\\/schema\\\/person\\\/2fe1805293ddcc967e4bd9e8afc50294\",\"name\":\"Molly Doyle\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/b9db24e2e72277a0449a8b18be06d377923ec2d6246b36613db304f58b586baf?s=96&d=mm&r=g\",\"url\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/b9db24e2e72277a0449a8b18be06d377923ec2d6246b36613db304f58b586baf?s=96&d=mm&r=g\",\"contentUrl\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/b9db24e2e72277a0449a8b18be06d377923ec2d6246b36613db304f58b586baf?s=96&d=mm&r=g\",\"caption\":\"Molly Doyle\"},\"url\":\"https:\\\/\\\/www.constructionspecifier.com\\\/author\\\/molly\\\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"To Vent or Not to Vent: Tips for insulating vented attics - The Construction Specifier","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\/","og_locale":"en_US","og_type":"article","og_title":"To Vent or Not to Vent: Tips for insulating vented attics - The Construction Specifier","og_description":"Designers have long used cross-ventilation to minimize the potential for moisture accumulation and condensation in attics and crawl spaces. However, unvented attics have become popular in both residential and commercial applications, pushed by emerging claims of energy savings and moisture control. While these \u2018new-style\u2019 attics can be successfully used in many circumstances, this author believes there are reasons to employ vented assemblies in many situations.","og_url":"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\/","og_site_name":"The Construction Specifier","article_published_time":"2013-07-12T20:13:58+00:00","article_modified_time":"2014-05-12T20:22:50+00:00","author":"Molly Doyle","twitter_card":"summary_large_image","twitter_misc":{"Written by":"Molly Doyle","Est. reading time":"1 minute"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\/#article","isPartOf":{"@id":"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\/"},"author":{"name":"Molly Doyle","@id":"https:\/\/www.constructionspecifier.com\/#\/schema\/person\/2fe1805293ddcc967e4bd9e8afc50294"},"headline":"To Vent or Not to Vent: Tips for insulating vented attics","datePublished":"2013-07-12T20:13:58+00:00","dateModified":"2014-05-12T20:22:50+00:00","mainEntityOfPage":{"@id":"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\/"},"wordCount":192,"commentCount":0,"publisher":{"@id":"https:\/\/www.constructionspecifier.com\/#organization"},"keywords":["07 57 13?Sprayed Polyurethane Foam Roofing","B1020.90?Roof Construction Supplementary Components","International Energy Conservation Code","International Residential Code","Sprayed polyurethane foam","Unvented attics","Vented attics"],"articleSection":["MasterFormat","UniFormat","07 00 00 Thermal and Moisture Protection","07 50 00 Membrane Roofing","B1020\u2212Roof Construction","B10\u2212Superstructure"],"inLanguage":"en-US","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\/#respond"]}]},{"@type":"WebPage","@id":"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\/","url":"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\/","name":"To Vent or Not to Vent: Tips for insulating vented attics - The Construction Specifier","isPartOf":{"@id":"https:\/\/www.constructionspecifier.com\/#website"},"datePublished":"2013-07-12T20:13:58+00:00","dateModified":"2014-05-12T20:22:50+00:00","breadcrumb":{"@id":"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\/#breadcrumb"},"inLanguage":"en-US","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\/"]}]},{"@type":"BreadcrumbList","@id":"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/www.constructionspecifier.com\/"},{"@type":"ListItem","position":2,"name":"To Vent or Not to Vent: Tips for insulating vented attics"}]},{"@type":"WebSite","@id":"https:\/\/www.constructionspecifier.com\/#website","url":"https:\/\/www.constructionspecifier.com\/","name":"The Construction Specifier","description":"Solutions for the Construction Industry","publisher":{"@id":"https:\/\/www.constructionspecifier.com\/#organization"},"potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.constructionspecifier.com\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-US"},{"@type":"Organization","@id":"https:\/\/www.constructionspecifier.com\/#organization","name":"The Construction Specifier","url":"https:\/\/www.constructionspecifier.com\/","logo":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/www.constructionspecifier.com\/#\/schema\/logo\/image\/","url":"https:\/\/www.constructionspecifier.com\/wp-content\/uploads\/2017\/09\/CS_Logo_BW_LR.jpg","contentUrl":"https:\/\/www.constructionspecifier.com\/wp-content\/uploads\/2017\/09\/CS_Logo_BW_LR.jpg","width":288,"height":70,"caption":"The Construction Specifier"},"image":{"@id":"https:\/\/www.constructionspecifier.com\/#\/schema\/logo\/image\/"}},{"@type":"Person","@id":"https:\/\/www.constructionspecifier.com\/#\/schema\/person\/2fe1805293ddcc967e4bd9e8afc50294","name":"Molly Doyle","image":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/secure.gravatar.com\/avatar\/b9db24e2e72277a0449a8b18be06d377923ec2d6246b36613db304f58b586baf?s=96&d=mm&r=g","url":"https:\/\/secure.gravatar.com\/avatar\/b9db24e2e72277a0449a8b18be06d377923ec2d6246b36613db304f58b586baf?s=96&d=mm&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/b9db24e2e72277a0449a8b18be06d377923ec2d6246b36613db304f58b586baf?s=96&d=mm&r=g","caption":"Molly Doyle"},"url":"https:\/\/www.constructionspecifier.com\/author\/molly\/"}]}},"views":5420,"publishpress_future_workflow_manual_trigger":{"enabledWorkflows":[]},"_links":{"self":[{"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/posts\/3707","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/users\/4"}],"replies":[{"embeddable":true,"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/comments?post=3707"}],"version-history":[{"count":3,"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/posts\/3707\/revisions"}],"predecessor-version":[{"id":3713,"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/posts\/3707\/revisions\/3713"}],"wp:attachment":[{"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/media?parent=3707"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/categories?post=3707"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/tags?post=3707"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}