{"id":3710,"date":"2013-07-12T16:17:44","date_gmt":"2013-07-12T20:17:44","guid":{"rendered":"http:\/\/www.constructionspecifier.com\/?p=3710"},"modified":"2017-01-20T11:14:13","modified_gmt":"2017-01-20T16:14:13","slug":"to-vent-or-not-to-vent-qa","status":"publish","type":"post","link":"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-qa\/","title":{"rendered":"To Vent or Not to Vent: Q&#038;A"},"content":{"rendered":"<p><strong>Q:<\/strong> When insulating an unvented attic assembly in a retrofit, what does one do with the existing blown-in insulation on the floor of the attic?<br \/>\n<strong>A:<\/strong> In an unvented attic assembly, conditioned air from the living space below should slowly infiltrate the attic space. Therefore, the fiberglass insulation would be removed.<\/p>\n<p><strong>Q:<\/strong> What happens if the blown-in insulation is left in place?<br \/>\n<strong>A:<\/strong> The blown-in insulation slows the heat transfer into the attic so the space is hotter in the summer and colder in the winter. Without the blown in insulation, the energy efficiency is better since the space is typically within 2 to 3 C (5 to 7 F) of the interior temperature.<\/p>\n<p><strong>Q: <\/strong>What is the best way to insulate an attic space if there is no ductwork or HVAC equipment within it?<br \/>\n<strong>A:<\/strong> A vented attic assembly would be more efficient if there is no ductwork or HVAC equipment in the attic. However, it is important to remember to air-seal the floor of the attic to minimize heat transfer through gaps, cracks, and voids from penetrations to the attic space.<\/p>\n<p>To read the full article, click <a href=\"http:\/\/www.constructionspecifier.com\/masterformat\/to-vent-or-not-to-vent-deciding-what-is-best-for-attic-applications\/\">here<\/a>.<\/p>\n<p>To read the other sidebar, click <a href=\"http:\/\/www.constructionspecifier.com\/masterformat\/to-vent-or-not-to-vent-tips-for-insulating-vented-attics\/\">here<\/a>.<\/p>\n","protected":false},"excerpt":{"rendered":"<p>Designers have long used cross-ventilation to minimize the potential for moisture accumulation and condensation in attics and crawl spaces. However, unvented attics have become popular in both residential and commercial applications, pushed by emerging claims of energy savings and moisture control. <\/p>\n","protected":false},"author":4,"featured_media":0,"comment_status":"open","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[520,179,449,187,268,487,459],"tags":[579,883,884,885,886,887,888],"class_list":["post-3710","post","type-post","status-publish","format-standard","hentry","category-features","category-masterformat","category-uniformat","category-07-00-00-thermal-and-moisture-protection","category-07-50-00-membrane-roofing","category-b1020roof-construction","category-b10superstructure","tag-07-57-13sprayed-polyurethane-foam-roofing","tag-b1020-90roof-construction-supplementary-components","tag-international-energy-conservation-code","tag-international-residential-code","tag-sprayed-polyurethane-foam","tag-unvented-attics","tag-vented-attics","entry"],"acf":[],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v28.9 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>To Vent or Not to Vent: Q&amp;A - The Construction Specifier<\/title>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-qa\/\" \/>\n<meta property=\"og:locale\" content=\"en_US\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"To Vent or Not to Vent: Q&amp;A - The Construction Specifier\" \/>\n<meta property=\"og:description\" content=\"Designers have long used cross-ventilation to minimize the potential for moisture accumulation and condensation in attics and crawl spaces. However, unvented attics have become popular in both residential and commercial applications, pushed by emerging claims of energy savings and moisture control.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-qa\/\" \/>\n<meta property=\"og:site_name\" content=\"The Construction Specifier\" \/>\n<meta property=\"article:published_time\" content=\"2013-07-12T20:17:44+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2017-01-20T16:14:13+00:00\" \/>\n<meta name=\"author\" content=\"Molly Doyle\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"Molly Doyle\" \/>\n\t<meta name=\"twitter:label2\" content=\"Est. reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"1 minute\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/to-vent-or-not-to-vent-qa\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/to-vent-or-not-to-vent-qa\\\/\"},\"author\":{\"name\":\"Molly Doyle\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#\\\/schema\\\/person\\\/2fe1805293ddcc967e4bd9e8afc50294\"},\"headline\":\"To Vent or Not to Vent: Q&#038;A\",\"datePublished\":\"2013-07-12T20:17:44+00:00\",\"dateModified\":\"2017-01-20T16:14:13+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/to-vent-or-not-to-vent-qa\\\/\"},\"wordCount\":201,\"commentCount\":0,\"publisher\":{\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#organization\"},\"keywords\":[\"07 57 13?Sprayed Polyurethane Foam Roofing\",\"B1020.90?Roof Construction Supplementary Components\",\"International Energy Conservation Code\",\"International Residential Code\",\"Sprayed polyurethane foam\",\"Unvented attics\",\"Vented attics\"],\"articleSection\":[\"Features\",\"MasterFormat\",\"UniFormat\",\"07 00 00 Thermal and Moisture Protection\",\"07 50 00 Membrane Roofing\",\"B1020\u2212Roof Construction\",\"B10\u2212Superstructure\"],\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\\\/\\\/www.constructionspecifier.com\\\/to-vent-or-not-to-vent-qa\\\/#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/to-vent-or-not-to-vent-qa\\\/\",\"url\":\"https:\\\/\\\/www.constructionspecifier.com\\\/to-vent-or-not-to-vent-qa\\\/\",\"name\":\"To Vent or Not to Vent: Q&A - The Construction Specifier\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#website\"},\"datePublished\":\"2013-07-12T20:17:44+00:00\",\"dateModified\":\"2017-01-20T16:14:13+00:00\",\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/to-vent-or-not-to-vent-qa\\\/#breadcrumb\"},\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/www.constructionspecifier.com\\\/to-vent-or-not-to-vent-qa\\\/\"]}]},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/to-vent-or-not-to-vent-qa\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/www.constructionspecifier.com\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"To Vent or Not to Vent: Q&#038;A\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#website\",\"url\":\"https:\\\/\\\/www.constructionspecifier.com\\\/\",\"name\":\"The Construction Specifier\",\"description\":\"Solutions for the Construction Industry\",\"publisher\":{\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#organization\"},\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/www.constructionspecifier.com\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-US\"},{\"@type\":\"Organization\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#organization\",\"name\":\"The Construction Specifier\",\"url\":\"https:\\\/\\\/www.constructionspecifier.com\\\/\",\"logo\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#\\\/schema\\\/logo\\\/image\\\/\",\"url\":\"https:\\\/\\\/www.constructionspecifier.com\\\/wp-content\\\/uploads\\\/2017\\\/09\\\/CS_Logo_BW_LR.jpg\",\"contentUrl\":\"https:\\\/\\\/www.constructionspecifier.com\\\/wp-content\\\/uploads\\\/2017\\\/09\\\/CS_Logo_BW_LR.jpg\",\"width\":288,\"height\":70,\"caption\":\"The Construction Specifier\"},\"image\":{\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#\\\/schema\\\/logo\\\/image\\\/\"}},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.constructionspecifier.com\\\/#\\\/schema\\\/person\\\/2fe1805293ddcc967e4bd9e8afc50294\",\"name\":\"Molly Doyle\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/b9db24e2e72277a0449a8b18be06d377923ec2d6246b36613db304f58b586baf?s=96&d=mm&r=g\",\"url\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/b9db24e2e72277a0449a8b18be06d377923ec2d6246b36613db304f58b586baf?s=96&d=mm&r=g\",\"contentUrl\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/b9db24e2e72277a0449a8b18be06d377923ec2d6246b36613db304f58b586baf?s=96&d=mm&r=g\",\"caption\":\"Molly Doyle\"},\"url\":\"https:\\\/\\\/www.constructionspecifier.com\\\/author\\\/molly\\\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"To Vent or Not to Vent: Q&A - The Construction Specifier","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-qa\/","og_locale":"en_US","og_type":"article","og_title":"To Vent or Not to Vent: Q&A - The Construction Specifier","og_description":"Designers have long used cross-ventilation to minimize the potential for moisture accumulation and condensation in attics and crawl spaces. However, unvented attics have become popular in both residential and commercial applications, pushed by emerging claims of energy savings and moisture control.","og_url":"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-qa\/","og_site_name":"The Construction Specifier","article_published_time":"2013-07-12T20:17:44+00:00","article_modified_time":"2017-01-20T16:14:13+00:00","author":"Molly Doyle","twitter_card":"summary_large_image","twitter_misc":{"Written by":"Molly Doyle","Est. reading time":"1 minute"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-qa\/#article","isPartOf":{"@id":"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-qa\/"},"author":{"name":"Molly Doyle","@id":"https:\/\/www.constructionspecifier.com\/#\/schema\/person\/2fe1805293ddcc967e4bd9e8afc50294"},"headline":"To Vent or Not to Vent: Q&#038;A","datePublished":"2013-07-12T20:17:44+00:00","dateModified":"2017-01-20T16:14:13+00:00","mainEntityOfPage":{"@id":"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-qa\/"},"wordCount":201,"commentCount":0,"publisher":{"@id":"https:\/\/www.constructionspecifier.com\/#organization"},"keywords":["07 57 13?Sprayed Polyurethane Foam Roofing","B1020.90?Roof Construction Supplementary Components","International Energy Conservation Code","International Residential Code","Sprayed polyurethane foam","Unvented attics","Vented attics"],"articleSection":["Features","MasterFormat","UniFormat","07 00 00 Thermal and Moisture Protection","07 50 00 Membrane Roofing","B1020\u2212Roof Construction","B10\u2212Superstructure"],"inLanguage":"en-US","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-qa\/#respond"]}]},{"@type":"WebPage","@id":"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-qa\/","url":"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-qa\/","name":"To Vent or Not to Vent: Q&A - The Construction Specifier","isPartOf":{"@id":"https:\/\/www.constructionspecifier.com\/#website"},"datePublished":"2013-07-12T20:17:44+00:00","dateModified":"2017-01-20T16:14:13+00:00","breadcrumb":{"@id":"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-qa\/#breadcrumb"},"inLanguage":"en-US","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-qa\/"]}]},{"@type":"BreadcrumbList","@id":"https:\/\/www.constructionspecifier.com\/to-vent-or-not-to-vent-qa\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/www.constructionspecifier.com\/"},{"@type":"ListItem","position":2,"name":"To Vent or Not to Vent: Q&#038;A"}]},{"@type":"WebSite","@id":"https:\/\/www.constructionspecifier.com\/#website","url":"https:\/\/www.constructionspecifier.com\/","name":"The Construction Specifier","description":"Solutions for the Construction Industry","publisher":{"@id":"https:\/\/www.constructionspecifier.com\/#organization"},"potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.constructionspecifier.com\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-US"},{"@type":"Organization","@id":"https:\/\/www.constructionspecifier.com\/#organization","name":"The Construction Specifier","url":"https:\/\/www.constructionspecifier.com\/","logo":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/www.constructionspecifier.com\/#\/schema\/logo\/image\/","url":"https:\/\/www.constructionspecifier.com\/wp-content\/uploads\/2017\/09\/CS_Logo_BW_LR.jpg","contentUrl":"https:\/\/www.constructionspecifier.com\/wp-content\/uploads\/2017\/09\/CS_Logo_BW_LR.jpg","width":288,"height":70,"caption":"The Construction Specifier"},"image":{"@id":"https:\/\/www.constructionspecifier.com\/#\/schema\/logo\/image\/"}},{"@type":"Person","@id":"https:\/\/www.constructionspecifier.com\/#\/schema\/person\/2fe1805293ddcc967e4bd9e8afc50294","name":"Molly Doyle","image":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/secure.gravatar.com\/avatar\/b9db24e2e72277a0449a8b18be06d377923ec2d6246b36613db304f58b586baf?s=96&d=mm&r=g","url":"https:\/\/secure.gravatar.com\/avatar\/b9db24e2e72277a0449a8b18be06d377923ec2d6246b36613db304f58b586baf?s=96&d=mm&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/b9db24e2e72277a0449a8b18be06d377923ec2d6246b36613db304f58b586baf?s=96&d=mm&r=g","caption":"Molly Doyle"},"url":"https:\/\/www.constructionspecifier.com\/author\/molly\/"}]}},"views":5380,"publishpress_future_workflow_manual_trigger":{"enabledWorkflows":[]},"_links":{"self":[{"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/posts\/3710","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/users\/4"}],"replies":[{"embeddable":true,"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/comments?post=3710"}],"version-history":[{"count":4,"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/posts\/3710\/revisions"}],"predecessor-version":[{"id":25660,"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/posts\/3710\/revisions\/25660"}],"wp:attachment":[{"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/media?parent=3710"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/categories?post=3710"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.constructionspecifier.com\/wp-json-v2\/wp\/v2\/tags?post=3710"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}