Tag Archives: Walls

Metal Wall Panels on the Roof: How to achieve durability and reliability using sheet metal

All images courtesy Simpson Gumpertz & Heger

All images courtesy Simpson Gumpertz & Heger

by Scott A. Tomlinson, PE, and Matthew M. Copeland, PE

Sheet metal has been used as a roofing material for centuries on all types of structures. Copper, stainless and galvanized steel, aluminum, and zinc are commonly employed in various low- and steep-slope assemblies. Designers and contractors know from centuries of accumulated knowledge how to achieve durable and reliable roofing assemblies using these types of sheet metal. But what about newer materials?

Modern architectural designs often use newer materials and metal panel assemblies for roofing applications, some of which are not intended to be used as roofing and, therefore, may not be well-suited for it. One such trend is the use of architectural metal wall panels (e.g. metal composite material [MCM]) as roofing to create a visually seamless transition between building walls and roof surfaces, such as low-slope setbacks in the façade. Whether in low- or steep-slope assemblies, using metal wall panels in roof applications presents unique challenges for the designer and contractor.

This article focuses on use of architectural metal wall panels in low-slope ‘brow’ roofing (Figure 1). It also includes a brief discussion of contractor coordination essential to success, particularly since metal wall panel contractors typically have a different set of skills and training than roofing contractors. The installation of metal wall panels on larger low-slope roof areas includes additional complications and risks not discussed in this article.

Generally, architectural metal wall panels are not well-suited for roofing applications. Even in vertical applications, these systems are not typically intended to be watertight. The systems incorporate water management strategies and a water-resistive barrier (WRB) behind the panels (i.e. a rainscreen) to accommodate water that penetrates the panels. It is unreasonable to expect these same panel systems and water-resistive barriers to be watertight when installed nearly horizontal and skyward-facing.

Therefore, the panels must be considered a water-shedding layer, much like roofing shingles, and roofing underlayment is required to accommodate water that penetrates the panel system. The underlayment must be designed and constructed to perform as ‘waterproofing.’ Self-adhering membrane roofing underlayment (referred to as a ‘membrane’ in this article) is well-suited for this application.

Panel skyward-facing surface water management
The panels should be considered the water-shedding layer and the roofing underlayment the primary waterproofing. That said, the panels should be designed and installed to shed as much water as practical to drainage locations and minimize water penetration to the waterproofing membrane. Allowing an excessive volume of water to penetrate the panel system to the membrane increases the risk of leakage through panel attachments, vulnerable details, and construction imperfections in the membrane system. Providing the maximum slope permitted by the design generally directs water away from vulnerable flashings and joints, and decreases water penetration through the panel system.CS_September_2014.indd

Providing a gutter system underneath skyward-facing panel joints (e.g. using splines in panel joints to create a gutter) and sealing the joints (e.g. sealant and backer rod if aesthetically acceptable) minimizes water penetration to the membrane (Figure 2); gutters should be used when possible. Depending on the roof geometry, some assemblies may not accommodate gutters underneath the joints because there is no place to drain water in the gutters; sealant should still be installed in these joints and should be maintained over time as the joints deteriorate. Returns at panel joints should be used to form gutters and receive sealant.

Panel internal vs. eave edge drainage
Sloping the panels to drain over edges is preferred to internally draining the roof. Systems that drain over edges more readily accommodate steep slopes, and minimize water penetration to the membrane (i.e. water does not have to flow to a drain in the membrane). Further, sloping of the panel planes and valleys is simpler because they do not need to conduct water to drain holes. Properly designed snow guards can mitigate the risk of falling snow and ice in colder climates.

Where draining to the exterior wall is unacceptable, the design must incorporate internal drainage or a perimeter gutter. Roof drains must provide drainage at both panel and membrane levels. One option is to provide a drain at the membrane level and holes in the panels directly over the drains (covered with perforated metal—additional ultraviolet [UV] protection of the membrane below may be required). Bi-level drains can also be used. The drains must be installed at the low points in the roof system. Slope and valleys in the panel system must direct water to the drain holes. Designers should consider heat tracing the drains where water can freeze and impede drainage (i.e. at canopy conditions where the drains do not enter heated space).

When a perimeter gutter system is used, the membrane and panels must integrate with the gutters. However, this detailing has intricacies beyond this article’s scope.

Panel impact on membrane level drainage
Unimpeded water drainage is critical at both the panel and membrane surfaces. The risk of water leakage through the self-adhering membrane (e.g. through weak seams, holes, and other imperfections) rises as the water’s volume, depth, and dwell time on the membrane increases.

Panel edges returned to form joints and gutters, and to receive sealant joints, should not extend all the way to the membrane surface. There should be a gap provided between the bottom edge of the return and self-adhering membrane to allow for drainage and reduce the risk of damage to the self-adhering membrane. The gap should be as large as practical (e.g. 25 mm [1 in.]), but not less than 6 mm (1/4 in.).

Panel attachment
The panels must be anchored to the roof structure to meet wind uplift and other loading requirements while maintaining the self-adhering membrane’s waterproofing integrity. Panel attachment clips are typically fastened with screws through the membrane to the structural sheathing or framing underneath the sheathing.

Panel attachment clips should be designed and positioned so they do not impede membrane level drainage. Using discrete clips (e.g. 100-mm [4-in.] long) in lieu of longer or continuous ones reduces the risk of impeding drainage. It is also important to install clips as far as practical away from drains and designed drainage paths such as valleys. This reduces the risk of impeding drainage and water leakage through the fastener penetrations, which are the weak point in the membrane system.

The clips should be fastened with wood screws to increase the likelihood of the membrane self-sealing to the fastener. The drilling action of self-drilling screws can damage the membrane and reduce the self-sealability.

Installing the clips on multiple pieces of membrane squares (e.g. 100-mm [4-in.] square, as shown in Figure 2) each, adhered to the layer below, increases the membrane thickness and self-sealability, and raises the elevation of the fastener penetrations above the membrane surface on which water flows. Setting the attachment clips in mastic atop the squares, before fastening, further increases the self-sealability of the fastener penetration.

A more reliable solution to attaching the panels with clips directly through the membrane waterproofing is to construct stanchions to which the panels are mounted. Stanchions provide penetrations that can be reliably waterproofed, but is a more custom assembly that increases the roof assembly’s overall thickness and cost.

Waterproofing materials
The waterproofing membrane is the critical component in a roof assembly using metal wall panels, and a self-adhering membrane is well suited for this application. Like most products, not all self-adhering membranes are equal. Some membranes form more reliable laps, adhere better, seal better around fasteners, are easier to handle and install, or can tolerate higher service temperatures.CS_September_2014.indd

Additionally, some membrane manufacturers have more ancillary products, technical support, and a longer track record of success. The designer must determine the appropriate membrane products, with the understanding it will be used as waterproofing.

Use self-adhering membrane designed for use as a roofing underlayment.
The membrane should meet ASTM D1970, Standard Specification for Self-adhering Polymer Modified Bituminous Sheet Materials Used as Steep Roofing Underlayment for Ice Dam Protection; the requirements for self-sealability and lap integrity under a head of water are particularly important. More flexible membranes are typically better for detailing, but can be more difficult to install.

The designer should consider specifying flood testing of the installed membrane. Also, it is important to note these products function as vapor retarders—therefore, the system as a whole must be evaluated for condensation resistance.

Specify rubberized asphalt-based adhesive instead of butyl-based adhesive where service temperature and compatibility permits.
It is the authors’ experience rubberized asphalt adhesive achieves higher initial and long-term adhesion. Substrates should be primed to improve membrane bond, even when not required by the membrane manufacturer.

Specify mastic and fluid-applied membrane at seams and details.
The membrane must be installed watertight on its own, but mastic installed over the membrane at seams and details can provide an additional layer of protection. Fluid-applied membrane can be installed underneath the membrane to form smooth transitions (e.g. cants) at inside corner details and to make three-dimensional details watertight.

Waterproofing installation
The self-adhering membrane must be properly installed to perform as waterproofing. The membrane system (and panel system flashing) must turn up building walls and integrate with flashings and the air/water/vapor barrier on the walls. The membrane must be uninterrupted by metal flashings so it is fully waterproof.

Slope
The membrane must be sloped to the drains (internally drained) or eave edges (edge drained). For an edge-drained system, the design must incorporate a gap at the eave edges to allow water on the membrane to drain out of the roofing assembly. The 2012 International Building Code (IBC) requires a minimum of 1/4 in. per ft for roofs—more slope is generally better. This minimum slope must be provided at the membrane level, which serves as the primary waterproofing (Figure 3), but should also be provided at the skyward-facing panel surface to help reduce water infiltration down to the membrane.

Substrate preparation
The substrate must be properly supported and attached and have smooth transitions at joints to prevent damage to the membrane during service. Uneven transitions and gaps should be bridged with sheet metal well-fastened to limit thermal movement that can cut the membrane. A fluid-applied cant improves seam reliability by easing the membrane transition and allowing the installer to apply the required pressure to form a reliable seal at seams. CS_September_2014.indd

Proper adhesion and reliable seams
Self-adhering membrane must be ‘fully’ supported and adhered to provide effective waterproofing and reliable seams. The substrate must be clean and dry, and the membrane must be firmly ‘pressed’ onto the substrate; hard rollers can help.

The pieces of membrane must be ‘fully’ adhered to each other at seams with no pathways for water (e.g. wrinkles).

Serviceability
Roof drains require maintenance. The hole in the panels at drains must be covered with a perforated material; this cover must be removable to allow maintenance workers to access and maintain the drain.

Metal wall panels are not designed to accommodate live loads imposed by maintenance workers in a horizontal application. If sealant joints and drains cannot be serviced without walking or kneeling on the panels, the designer should consider methods of providing supplemental panel support and/or maintenance worker load distribution.

The authors have considered using moisture-tolerant high-load capacity rigid insulation over drainage mat between the top of the self-adhering membrane and the underside of the panels (fit snugly) to provide additional support. However, such a system has yet to be installed or tested.

Contractor co-ordination
Critical to the successful performance of a metal wall panel low-slope roof is both the designer and contractor believing the panels must minimize water penetration to the membrane, and the membrane must perform as ‘waterproofing.’

A pre-construction meeting is beneficial to clarify design intent and project requirements. The pre-construction meeting should include the:

  • designer;
  • general contractor;
  • metal panel subcontractor;
  • subcontractor responsible for installing the membrane; and
  • other involved contractors.

The meeting should include discussion of the following:

  1. The designer and contractor must understand the panels are a first line of defense intended to shed water and minimize the volume of water that reaches the membrane. The panels themselves are impermeable, but the joints and flashing, even if protected with gutters and sealants, will permit water penetration through the panel system. Water penetration will increase as sealants deteriorate.
  2. The construction schedule should allow adequate time for inspection of the membrane installation before installation of any overlying materials, including any mastics/sealants applied over seams in the membrane (i.e. membrane must be inspected prior to applying mastics/sealants). The membrane installation must be watertight on its own; flood testing requirements need to be coordinated with the project team at the pre-construction meeting. The designer and contractor should expect that water will pond on the membrane under certain conditions.
  3. Panel shop drawings must be coordinated with the roofing design and installation so water drainage is directed to the appropriate location. For example, panel valleys should conduct water directly to the drains, not simply to their general vicinity. Shop drawings should indicate location and size of metal panel anchors as well as joints between panels. Perimeter flashing and other transitions to adjacent construction should be coordinated on the shop drawings, with clear indication of responsibility. Adequate coordination may require additional effort on behalf of the general contractor.

Conclusion
Architectural metal wall panels can be used with success in a low-slope roofing application with proper design and construction. Success requires the designer, contractor, and end user to understand the panels are a first line of defense intended to shed as much water as practical, while the self-adhering membrane level must be designed and installed as waterproofing. Additionally, the system must be maintained. Sealant joints require regular inspection and replacement, and drains demand cleaning.

Before designing and constructing a roofing system using architectural metal wall panels, the owner and designer must be aware of the risks. These include leakage, warranty implications (i.e. will leakage be covered by a long-term warranty?), and cost of repair. In some instances, the risks may be more than the designer and/or owner can tolerate.

Scott A. Tomlinson, PE, is a senior project manager at Simpson Gumpertz & Heger Inc. (SGH), with more than 15 years of experience designing, constructing, investigating, and repairing building-envelope systems of all types. He can be reached at satomlinson@sgh.com.

Matthew M. Copeland, PE, is a senior staff I at SGH, with more than eight years of experience. He specializes in the design, investigation, and rehabilitation of building envelope systems for both historic and contemporary structures, with a focus on materials science issues. Copeland can be contacted via e-mail at mmcopeland@sgh.com.

 

Abst

Standards and Terminologies

In the May 2014 issue of The Construction Specifier, we published the article, “Passive Fire Protection and Interior Wall Assemblies,” by Gregg Stahl. Soon after, a reader contacted us regarding what he considered inaccuracies. We reached out to the author and, in the interest of continuing the discourse about this important topic, excerpts from both sides are included below.

Reader: The first issue is the reference to ASTM E603. The author mentions this is one of two standards that rates assemblies. Actually, ASTM E603 is a “guide” standard, and is used to explain the various types of fire tests, whether they are ASTM, NFPA, UL, or FM, and how they can be compared and contrasted. This standard is not a test method.
Author: The reader brings up several good points in regard to the article on passive fire protection. It should be noted, however, this piece was intended to provide a general overview on the basic principles of passive fire protection. As to the first point, the reader is technically correct. E603 is in fact an ASTM “Guide,” not an ASTM “Standard.” In the “Scope” section of this guide, it does state one of the purposes is to “allow(s) users to obtain fire-test-response characteristics of materials, products, or assemblies, which are useful data for describing or appraising their fire performance under actual fire conditions.” In the subsequent paragraphs, I go on to describe how A603 is used as well as differentiating it from the E119 fire test, which is testing the effectiveness of a particular assembly.

Reader: The second issue is the article states ASTM E119 tests the effectiveness of an assembly as a “fire barrier.” Although not untrue, the use of “fire barrier” seems to limit the type of fire-rated assembly that is tested, since a “fire barrier” is a specific type of fire-rated assembly used by the IBC and NFPA. ASTM E119 is used to test any type of assembly for fire-resistance, whether it is a wall, roof system, floor system, column, beam, etc.
Author: I should have been more precise in the selection of the terminology used. The intent of the term was to use a dictionary meaning, not a fire test assembly meaning. A Google search for the term will produce numerous definitions, such as the one below:

fire barrier: a continuous vertical or horizontal assembly, such as a wall or floor, that is designed and constructed with a specified fire resistance rating to limit the spread of fire and that also will restrict the movement of smoke. Such barriers might have protected openings.

Reader: The third issue is mentioning the hose stream test is used to “measure an assembly’s resistance to water pressure.” This is misleading. The hose stream test is not really a measure of an assembly’s resistance to water pressure, but to test the system’s integrity. As the commentary to the standard states, the hose stream tests the “ability of the construction to resist disintegration under adverse conditions.” In other words, it is a way of testing, from a distance (it is very hot) the assembly’s integrity from falling debris.
Author: The reader references “the standard,” but I do not know to which standard he is referring. ASTM E2226, Standard Practice for Application of Hose Stream, states:

1.3 – The result derived from this practice is one factor in assessing the integrity of building elements after fire exposure. The practice prescribes a standard hose stream exposure for comparing performance of building elements after fire exposure and evaluates various materials and construction techniques under common conditions.

The application of the hose stream does exert pressure on the assembly after it has completed either the full cycle of an E119 fire test or 50 percent of the time of the rated wall assembly. I agree the single word “pressure” does not go far enough to explain—the intent was to determine the integrity of the remaining assembly.

Reader: The fourth and final issue is the use of “area separation firewalls” in the article, and its associated endnote. The use of “area separation” walls was dropped when the IBC was published in 2000, and is not a term used by NFPA’s standards. The correct term used by both the IBC and NFPA is “fire wall” (not a single word). The endnote (no. 3) gives the impression these “area separation firewalls” are used to separate residential units or commercial tenants. This is incorrect. A fire wall divides a building—residential or commercial—into separate buildings so they can be considered independently when applying the code. “Fire partitions” are used for residential unit and commercial tenant separations within a single building and do not require the type of requirements described in the article.
Author: I respectfully disagree with the reader, who seems to be making the reference to area separation walls fit his use without recognizing the term can have more than one use or intent. It was employed here with no reference to NFPA or IBC, and was not intended as the reader interpreted it.
The term “area separation wall”—or “ASW” as it is commonly abbreviated—is used for a particular type of fire-rated wall assembly with a two-hour fire resistance rating, which is typically intended to permit controlled collapse of one unit in a multifamily residence, while still remaining intact and able to protect the adjacent unit in a fire situation. This is a common term in the construction industry. The reader can check the literature of various manufacturers and find this type of assembly. There are also various UL assemblies for this type of construction.

Clarification on wall systems article

The April 2013 issue of The Construction Specifier included a technical feature by J.W. Mollohan, CSI, CCPR, CEP, LEED GA, entitled, “Exterior Wall Assemblies: Are You Getting What You Specified?”  We received the following letter from Cliff Black, a CSI member and a building envelope product manager for Firestone Building Products.

I am writing in regard to the article on exterior wall assemblies. I agree with the author the issue is certainly a challenging one for the design and specifying community. I would like to cite the bracketed statement at the top of page 57, which states, “buildings of two stories or more.” This appears to be taken in the context of the design of National Fire Protection Association (NFPA) 285, Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of Exterior Non-load-bearing Wall Assemblies Containing Combustible Components, addressing multi-story fire propagation.

However, the International Building Code (IBC) 2603.5 states NFPA 285 is required for buildings of any height for Types I through IV construction incorporating combustible plastic insulation in the exterior wall assembly. IBC Chapter 14 (“Exterior Walls”) calls for differing requirements for water-resistant barriers (WRBs) and various combustible claddings, qualified by height.

In this case, I believe the statement should read “buildings of any height,” rather than “buildings of two stories or more.”

 

Mr. Mollohan replied to Mr. Black, and has allowed us to share it with other readers of the magazine:

 

Good catch, Clint! You are absolutely correct that one must be familiar with multiple chapters of the IBC to determine whether an NFPA 285 test is required. My error, and your correction, illustrates the difficulty of this provision. I am attaching an adaptation of a flow chart originally created by Barbara Horwitz-Bennett of DuPont Building Innovations for guidance to interested readers:

Diagram_edited-1

Passive Fire Protection and Interior Wall Assemblies

All images courtesy ClarkDietrich Building Systems

All images courtesy ClarkDietrich Building Systems

by Gregg Stahl

Integral to commercial building design, passive fire protection is a method for containing a blaze at its source, preventing the spread of flames and smoke throughout a building for a specified time so occupants can evacuate the structure.

Unlike active fire protection devices, such as sprinkler systems, fire alarms, and fire extinguishers, these passive fire protection systems utilize fire-resistant materials embedded in interior building assemblies, lying dormant and hidden from public view until a fire ‘calls’ them into action.

One of the most important areas of concentration for these passive fire protection design strategies is the wall assembly. To ensure optimal fire protection, the building codes require these assemblies to be evaluated by industry standards to determine their fire performance. This article provides examples of fire-rated wall assemblies and passive firestop systems. It also describes the testing they must go through to achieve their fire ratings while covering best practices for their specification and installation.

Fire-rated wall assemblies
Total passive fire protection cannot be achieved through the use of one product—it requires an assembly of several different fire-resistant materials that work together systematically to slow the passage of flames, smoke, and toxic gases. For example, most exterior and interior commercial wall assemblies feature light-gauge steel studs, fiberglass insulation, and gypsum wallboard, which are all materials possessing naturally high fire resistance. The three materials perform well together in wall assemblies and are used in various combinations of thickness and numbers of layers to increase fire resistance.

The fire resistance of wall assemblies is evaluated by two industry standards—ASTM E603, Standard Guide for Room Fire Experiments, and ASTM E119, Fire Tests of Building Construction and Materials. These standards rate the assemblies based on how many hours they prevent the passage of fire, heat, smoke, and gases.

The integration of intumescent firestop materials onto steel framing members is one of the most recent high-performance innovations in passive protection. Such products eliminate both overage and underage often associated with messy caulks and sprays.

The integration of intumescent firestop materials onto steel framing members is one of the most recent high-performance innovations in passive protection. Such products eliminate both overage and underage often associated with messy caulks and sprays.

ASTM E603 measures temperatures, smoke generation, ignition to flashover time, combustion gas, and total energy release as a fire moves from one room to the next. Referred to as the ‘room corner test,’ it involves a corner of a room constructed in an accredited testing facility, using standard building materials. Materials to be tested are mounted on the walls and ceiling of the room corner. A fire source, usually a wood crib or a diffusion burner, is placed in the corner and ignited. The test mimics a wastebasket-sized fire that spreads to something nearby. To achieve a satisfactory performance rating, the tested assembly must not allow the spread of smoke and fire or generate excessive amounts of smoke.

ASTM E119, on the other hand, establishes a wall assembly’s effectiveness to act as a fire barrier. In this case, a wall is tested for structural integrity and the ability to contain a fire for a quantified period. The assembly is mounted to a specially constructed furnace and gas burners are lit as thermocouples record temperatures and the flames mimic heat from an adjacent fire. Observations are made through viewing windows in the furnace and with instrumentation. Temperatures and the length of time before the system fails are recorded.

This test method uses a furnace-heating schedule, or timed increase of temperature, which brings the furnace up to 538 C (1000 F) in five minutes, up to 927 C (1700 F) in one hour, and to 1010 C (1850 F) in two hours. Assemblies must survive these temperatures to be successfully fire-rated by the standard. A hose stream test follows to measure the assembly’s resistance to water pressure after the burn.

Fire-resistant wall assembly examples
Non-combustible, non-load-bearing wall assemblies must be constructed from fire-resistant materials. All combinations of assemblies are tested to establish hourly fire ratings. In the following paragraphs, this article examines three common variations of such assemblies.

Typical one-hour-rated assembly, UL Design V450—non-combustible, non-loadbearing1
One layer of 15.9-mm (5/8-in.) Type X gypsum board2 is applied horizontally or vertically to either side of minimum 92-mm (3 5/8-in.) steel drywall framing spaced on 600-mm (24-in.) centers. Gypsum board is fastened to the steel studs using 25-mm (1-in.) Type S bugle-head steel screws at 200 mm (8 in.) on center (oc) perimeter and field for horizontal applications, or 200 mm oc perimeter and 300 mm (12 in.) oc field for vertical applications. Joints must be offset. For extra fire resistance, thermal resistance and acoustic control, add 89 mm (3 1/2 in.) of fiberglass batt insulation to the wall cavity.

Typical two-hour rated assembly, UL Design V450—non-combustible, non-loadbearing
Two layers of 15.9-mm (5/8-in.) Type X gypsum board is applied horizontally or vertically in accordance to the fire assembly to either side of minimum 63.5-mm (2 1/2-in.) steel drywall framings spaced on 600-mm (24-in.) centers. The base layer of gypsum board is fastened to the steel studs using 25-mm (1-in.) Type S bugle-head steel screws spaced 400 mm (16 in.) oc perimeter and field.

Track members having the intumescent material already integrated can provide up to 76 mm (3 in.) of total movement and up to three-hour fire-rated protection.

Track members having the intumescent material already integrated can provide up to 76 mm (3 in.) of total movement and up to three-hour fire-rated protection.

The same screw placement and use of a 130-mm (5 1/8-in.) screw apply to the face layer as well. Joints must be offset on the opposite sides of the wall and between layers. For extra fire resistance, thermal resistance, and acoustic control, 64 mm (2 1/2 in.) of fiberglass batt insulation can be added to the wall cavity.

Area separation firewalls
Another important assembly demanding fire resistance performance is the area separation firewall. These walls are required between adjacent apartments or townhouses, and in some cases, they are required in commercial and institutional buildings.3

The area separation wall is designed to allow for collapse of the construction on the fire-exposed side, without collapse of the entire wall. To do this, aluminum breakaway clips attach the separation wall to the adjacent framing. When one side of the separation wall is exposed to fire, the clips are designed to soften and break away. This allows the structure on the fire side of the separation wall to collapse, while the clips on the unexposed side of the separation wall continue to support the separation wall.

A typical area separation firewall assembly consists of two layers of 25 x 610-mm (1 x 24-in.) gypsum shaftliner panels inserted between floor and ceiling runners with steel H-studs installed between adjacent panels. A 19-mm (3/4-in.) air space must be maintained between steel components and adjacent framing. An 89-mm (3 1/2-in.) layer of fiberglass batt insulation in the wall cavity is also recommended.

Proper installation of a fire-rated assembly is important. Good construction practices—executed in accordance with manufacturers’ recommendations and the fire-rated assembly’s requirements—are needed to ensure the assembly built in the field is representative of the one tested. However, an additional passive firestop system is needed for these assemblies to seal off the passage of flames, smoke, and toxic gases through the joints and penetrations of a wall assembly.

Passive firestop systems
Penetrations are often made through fire-rated wall assemblies for switches, electrical boxes, power outlets, or the passage of pipes, cables, or HVAC ductwork. At these locations, as well as wherever there are wall perimeter joints, it is necessary to seal the openings off with firestop materials. There is no one universal product that will work for every firestop application. Traditionally, specified materials include:

  • sealants;
  • intumescent materials;
  • sprays (i.e. spray-applied compounds, usually latex or silicone-based, that provide firestopping through penetrations, voids, and construction joints of the wall assembly, framing, and ductwork); and
  • foam blocks or pillows (i.e. self-contained, intumescent firestop products for through-penetration, such as where ductwork or support beams pass through wall assemblies—on exposure to flames, they intumesce to form a hard char that tightly seals penetrations against flame spread, smoke, and toxic gases).

It is important to select products that have been appropriately tested to meet applicable fire safety standards.

Using a cured factory-metered dosage intumescent material, this profile provides firestopping and sound-dampening effective immediately as framing composite is installed.

Using a cured factory-metered dosage intumescent material, this profile provides firestopping and sound-dampening effective immediately as framing composite is installed.

Sealants
Sealants are the most recognized group of firestop products due to their versatility, as caulk can have various uses on construction projects, such as sealing penetrations and construction joints. These products are available in various forms and chemical formulations. Firestop sealants in caulk, self-leveling, and spray grade are readily available in silicone, latex, and solvent-based products. They often require the addition of a backing material (e.g. polyethylene backer rod) in the system for support.

Often, the effectiveness of their application is governed by the ambient temperature. Consequently, in unheated spaces during construction, this may be an issue.4 Additionally, any overlapping work from other subcontractors—such as previously installed mechanical ductwork or piping—can interfere with the sealants’ application and inspection.

Intumescent materials
Intumescent materials are firestop products that expand in volume when exposed to heat or flames exceeding a specified temperature. They are one of the primary groups of products employed in applications where one of the assembly components deteriorates or burns away during fire exposure or where surfaces are uneven and a tight fit is impossible.

The expansion of the material closes the void that is created when the item melts or burns away, maintaining the fire-rated assembly’s integrity. Intumescent firestop materials come in various forms, from caulks to metallic collars with intumescent strip linings, with each product being designed for a specific purpose.

Integrated firestop systems
The integration of intumescent firestop materials onto steel framing members is one of the most recent high-performance firestop innovations. In many commercial and institutional projects, architects and specifiers are now using steel tracks manufactured with a factory-metered dosage of intumescent material applied in a controlled environment to the track flanges. These products help architects specify product and assembly solutions for both hidden and exposed aesthetic conditions where fire, smoke, and sound resistance ratings are required.

Single-source construction of wall assemblies and installation of joint protection can now be achieved by drywall contractors, eliminating any trade overlap issues common to installing traditional firestop materials. Track members having the intumescent material already integrated can provide up to 76 mm (3 in.) of total movement and up to three-hour fire-rated protection.

These integrated firestop products are easier to install than traditional firestop materials. Contractors simply install the track member, which includes the intumescent tape, at the top, bottom, or sides of the wall. This eliminates the need to return and install intumescent caulking at a later time, eliminating multiple labor and material operations.

Passive firestop system evaluation

Integrated passive fireproofing systems, such as this one, provide several design advantages, including earlier and easier inspection as the system is installed and inspected as ‘joint framing’ (before obstructions).

Integrated passive fireproofing systems, such as this one, provide several design advantages, including earlier and easier inspection as the system is installed and inspected as ‘joint framing’ (before obstructions).

Like wall assemblies, the fire performance of passive firestop systems must also be evaluated by various industry standards. ASTM E1966, Standard Test Method for Fire-resistive Joint Systems, is one standard that covers sealants, coatings, and materials used in joints. ASTM E814, Fire Tests of Through Penetration Firestops, is the complementary test to ASTM E119 that evaluates penetrations through a tested, fire-resistive (i.e. ASTM E 119-tested) wall or floor assembly.

The test involves a standard time-temperature curve and a hose stream test; it assigns ratings based on ‘T’ (temperature rise) and ‘F’ (flame occurrence through the firestop/penetration). The objective of specifying this type of system is to return the floor or wall to the compartment’s original fire rating. An ‘L’ (air leakage) rating can also be assigned. Air leakage simulates smoke movement through a penetration, measured in cubic feet per minute.

Conclusion
Fire-rated wall assemblies and passive firestop systems are crucial elements in the design of all commercial buildings. They help increase occupant safety and allow project teams to meet building code requirements.

By following the guidelines for fire-rated wall assemblies and passive firestop systems, building and design professionals can produce interior walls that will help protect building occupants against flames and smoke for a specified time. Combined with active fire protection methods and occupant education, these passive fire protection techniques provide a safer, more balanced strategy for protecting a building and those inside.

Notes
1 Underwriters Laboratories refers to this design as BXUV.V450. For more, visit bit.ly/1e5sKvR. (back to top)
2 Type X is standard fire-resistant gypsum board. Type C offers stronger resistance. (back to top)
3 In general, the purpose of area separation walls is to provide extra fire resistance between adjoining residential or commercial building units. They impede sound transmission, as well as the spread of fire from one unit to the next. Not all commercial or institutional buildings are going to have multiple tenants. (back to top)
4 In the cooler seasons, installers may have to employ the use of temporary, portable heaters to reach the proper temperature to ensure sealant adhesion. However, contractors should be keenly aware of the safety concerns when using these instruments in the work environment. (back to top)

Gregg Stahl is the director of product development at ClarkDietrich Building Systems, a manufacturer of steel framing and finishing products for the commercial construction industry. With more than 25 years of industry experience, he has served in multiple capacities at ClarkDietrich, including vice president of its subsidiary Vinyl Corp. Stahl has also held various roles within sales and product management. He can be reached at gregg.stahl@clarkdietrich.com.